Submersible Pump Cable 1000 volts 90°C

Description
Three RWU-40 conductors cabled together with green insulated bonding wire. Extra thickness of FT1 rated flame retardant, low temperature, water and sun resistant XLPE insulation, coloured for identification. Rated 1000 volts. Maximum conductor temperature 90°C.

CSA Spec C22.2

Packaging: long lengths to cut.

Applications:

ECS
Catalogue
Number

Size

AWG

No. of
Cond.
Bonding Wire
Size/AWG*

Insulation
Thickness

(inches)

Approx. Overall
Diameter**
(inches)

Total
Weight
(lbs/km)

Ampacity
30°C
Ambient
(amps)
Colour Code
PMP12-04 12 (7) 3 14 (7) .060 .50 459 20 Blk/Red/Ylw/Grn
PMP12-04F 12 (7) 3 12 (7) .060 .52 466 20 Blk/Red/Ylw/Grn
PMP12-04-8 12 (7) 3 8 (7) .060 .58 650 20 Blk/Red/Ylw/Grn
PMP10-04 10 (7) 3 12 (7) .060 .55 640 30 Blk/Red/Ylw/Grn
PMP10-04-8 10 (7) 3 8 (7) .060 .62 787 30 Blk/Red/Ylw/Grn
PMP08-04 8 (7) 3 10 (7) .080 .70 1,017 40 Blk/Red/Ylw/Grn
PMP08-04F 8 (7) 3 8 (7) .080 .74 1,181 40 Blk/Red/Ylw/Grn
PMP06-04 6 (7) 3 8 (7) .080 .84 1,473 55 Blk/Red/Ylw/Grn
PMP04-04  ‡ 4 (7) 3 8 (7) .080 .90 2,040 70 Blk/Red/Ylw/Grn

 

* Most provincial inspection authorities require bonding conductors in accordance with the Canadian Electrical Code. Others, like Ontario and the Yukon, require #8 AWG. Check with your inspection department for local requirements.

** Approximate diameter of circumscribing circle.

‡ TWU-40 VOLTAGE RATING: 600V 60°C PVC

 

Applications:

Designed for use within the well casing to supply power to the submersible pump.