Fire Alarm Cable Unshielded 300V CMG FAS FT4 CSA

 

Solid bare copper conductors, PVC insulation, Red PVC jacket FT-4 -20° C to 105° C, 300 Volts, CSA Approved. UV Resistant, Exposed Wiring.

Applications:

ECS
Catalogue
Number
Conductor Wall Thickness Nominal
O.D.
(inches)
Total
Weight
(lbs/km)
Colour Code Chart
No. AWG
Size
Stranding Insulation
(inches)
Jacket
(inches)
FAG22-06CBO 6 22 Solid .015 .030 .225 113 7
FAG22-10CBO 10 22 Solid .015 .032 .275 173 7
FAG22-15CBO 15 22 Solid .015 .032 .321 240 7
FAG22-20CBO 20 22 Solid .015 .032 .360 307 7
FAG22-30CBO 30 22 Solid .015 .040 .443 460 7
FA18-02CBO 2 18 Solid .015 .030 .209 90 7
FAP18-02CBO* 2 18 Solid .015 .030 .131 X .203 75 7
FAG18-03CBO 3 18 Solid .015 .030 .224 120 7
FAG18-04CBO 4 18 Solid .015 .030 .238 147 7
FAG18-05CBO 5 18 Solid .015 .030 .255 173 7
FAG18-06CBO 6 18 Solid .015 .032 .271 200 7
FAG18-07CBO 7 18 Solid .015 .032 .289 219 7
FAG18-08CBO 8 18 Solid .015 .032 .302 253 7
FAG18-09CBO 9 18 Solid .015 .032 .316 273 7
FAG18-10CBO 10 18 Solid .015 .032 .330 307 7
FAG18-11CBO 11 18 Solid .015 .032 .340 324 7
FAG18-15CBO 15 18 Solid .015 .040 .403 460 7
FAG18-20CBO 20 18 Solid .015 .040 .454 593 7
FAG18-21CBO 21 18 Solid .015 .040 .460 608 7
FAG18-30CBO 30 18 Solid .015 .040 .535 842 7
FAG18-50CBO 50 18 Solid .015 .048 .692 1,375 7
FAP16-02CBO* 2 16 Solid .015 .035 .156 X .240 110 7
FA16-02CBO 2 16 Solid .015 .035 .244 110 7
FAG16-03CBO 3 16 Solid .015 .035 .254 147 7
FAG16-04CBO 4 16 Solid .015 .035 .279 184 7
FA14-02CBO 2 14 Solid .020 .040 .302 170 7
FAG14-03CBO 3 14 Solid .020 .040 .315 226 7
FAG14-04CBO 4 14 Solid .020 .040 .343 285 7

FA12-02CBO

2 12 Solid .020 .040 .340 256 7

 

Specifications and Compliances
  • CSA C22.2 No. 208, Fire alarm and signal cable (Type FAS105)
  • CSA C22.2 No. 2556, FT4 Vertical-Tray Flame Test
Conductor
    Solid Bare Soft Copper Conductors, ASTM B3
Insulation
    Polyvinyl Chloride (PVC) 105°C, 300V
Shielding
    Overall Shield with Tinned Copper Drain Wire
Jacket
    Flame Retardant Polyvinyl Chloride (PVC), Red

Applications:

  • For use in fire alarm, signal, and voice communication circuits where exposed, concealed, or used in raceways or indoors in dry or damp locations.
  • Refer to Section 32 of the Canadian Electrical Code for conductor size restrictions and limits of use of non-armoured constructions.